Sec. 5-916. - International Mechanical Code—Amended by adding section 1004.6.1 amended.

The 2018 International Mechanical Code is hereby amended by adding section 1004.6.1, which reads as follows: 1004.6.1 Emergency shutoff. Any boiler, whether for building heat or domestic hot water, having 200,000 BTU input and above, shall have an emergency shutoff located outside the boiler room. The switch must be labeled with a red tag and white letters that clearly read "EMERGENCY BOILER SHUTOFF." Exception: When approved by the state boiler inspector, the switch may be located inside the boiler room.