Sec. 5-914. - International Mechanical Code—Section 603.8 and 603.8.2 amended.
Section 603.8 and 603.8.2 of the 2018 International Mechanical Code is hereby amended to read as follows: 603.8 Underground ducts. Ducts shall be approved for underground installation. Metallic underground ducts shall be completely encased in a minimum of two inches (51 mm) of concrete. 603.8.2 Sealing. Ducts shall be sealed, secured, and tested prior to concrete encasement. Ducts shall be leak tested as required by section C403 of the 2018 International Energy Conservation Code.
(Code 2018, § 5-614)