§ 5-915 — International Mechanical Code—[BF] section 607.4 amended

Code of Ordinances of the City of Lawrence, Kansas (Codified through Ordinance No. 10209, enacted April 14, 2026 (Supp. No. 4)) · Lawrence Code of Ordinances § 5-915

Corpus is an independent public-information project, not the official City of Lawrence website. Stable reference: corpuslaw.us/code/1a44ae9a-107b-4777-8016-837ef8892c96

Sec. 5-915. - International Mechanical Code—[BF] section 607.4 amended.

[BF] section 607.4 of the 2018 International Mechanical Code is hereby amended to read as follows: [BF] 607.4 Access and identification. Fire and smoke dampers shall be provided with an approved means of access. To permit inspection and maintenance of the damper and its operating parts, there shall be a minimum of 144 square inches access; when the duct is less than 12 inches wide, for access, the duct shall be equipped with a removable section of duct. Ceiling access must have a minimum 18-inch by 18-inch access opening, with unobstructed access to the duct. The access shall not affect the integrity of fire-resistance-rated assemblies. The access openings shall not reduce the fire-resistance rating of the assembly. Access points shall be permanently identified on the exterior by a label having letters not less than 0.5 inch (12.7 mm) in height reading: FIRE/SMOKE DAMPER, SMOKE DAMPER or FIRE DAMPER. Access doors in ducts shall be tight fitting and suitable for the required duct construction.

(Code 2018, § 5-615)

Ask a question about Lawrence law

Corpus searches the Lawrence sections it holds and shows the ones that match, with their citations. Free, no sign-in.