§ 13-151 — - Units burning over 60 pounds per hour
Code of Ordinances of the City of Dearborn, Michigan (2026 S-07: Code and Zoning updated through September 22, 2026) · Dearborn City Code § 13-151
Corpus is an independent public-information project, not the official City of Dearborn website. Stable reference: corpuslaw.us/code/261d10e1-795a-4654-8343-350a7ef78af0
Sec. 13-151. - Units burning over 60 pounds per hour.
(a) The following requirements govern units burning over 60 pounds of refuse or debris per hour: commercial, industrial, municipal and special fuel burning units. All installations hereinafter erected shall be equipped with incinerators of a Class III to VII type, designed for the principal waste to be destroyed. They shall be of a heavy duty construction and shall include primary combustion chamber designed with a maximum heat release of eight Btu's per second per cubic feet, secondary combustion chamber to maintain 1,500 degrees Fahrenheit and final combustion chamber, wherein the gases shall not exceed 11 feet per second, calculated at 1,500 degrees Fahrenheit maximum fuel weight, to be destroyed on grates not to exceed 65 pounds per square foot per hour. Flue gas travel changes from primary chamber to breeching shall be 450 degrees. (b) Incinerators handling wet material shall add a drying hearth area designed for 25 pounds per hour per square feet of hearth and an additional 90 degrees gas directional change. (c) Material charging may be direct, side, end of top charge chutes no longer than one-half of the height of the incinerator. (d) Refractory linings shall be of a 33 to 34 P.C.E. minimum, using a 4½-inch lining up to nine square feet of grate burning area, nine-inch lining over nine square feet and 13½-inch lining on all walls over nine feet in height. (e) When a brick setting is used, a two-inch air space will be required between the lining and the exterior wall, or in lieu of masonry, a steel casing with two inches of approved insulation may be applied. (f) All Class III to VII types of incinerators shall have exterior structural steel framework designed to withstand interior thrusts and the necessary supports for doors and appurtenant assemblies. Type 1 fuel shall be burned on approved cast iron grates with cast iron supports. Grate openings are not to exceed 40 percent of total burning area. Grates may be stationary, mechanically or manually operated. All incinerators which destroy fuel or any type in sufficient quantities to be equal to or greater than 750,000 Btu's per hour input shall be equipped with the following: positive pressure overfire air, secondary fuel, photoelectric smoke indicator, and indicatory pyrometer. Refractory coating may also be necessary by the division in order to maintain maximum furnace temperatures. Type 2 fuel shall be burned on hot drying hearths with fuel grate burned on combination hot refractory drying hearth and cast iron grate area, each approximately 50 percent of total burning area. Type 4 shall be burned on hot refractory hearth area over the total burning area. Type 5 may be applied to standard type heavy duty incinerators with safety and automatic controls for firing. Type 6 fuel shall be burned on hot or cold refractory hearth or crucible with direct charging to burning area. Approved fly ash collection equipment must also be furnished in order to meet the requirements of this article. Units up to 400 pounds per hour total burning area may be manually operated and controlled, provided the user has an operator in attendance and a sufficient amount of the time during operation to guarantee functioning within the code limits. Units over 400 pounds per hour capacity, as rated under this article shall have control over auxiliary fuel, over fire air, photoelectric smoke indicator with suitable alarm and indicating pyrometer. All breeching shall be of high temperature construction refractory lined. Ash pits and secondary combustion chambers shall be lined with a minimum of two inches of approved insulation material when same is constructed on concrete slab. (g) The following details must also be included in the design: (1) Mean design 1,500 degrees Fahrenheit; (2) Secondary combustion chamber to have an area normal to gas path such that maximum furnace heat release will not exceed 850,000 Btu's per square foot of area, 25 feet per second; (3) Settling chamber to have an area normal to gas path such that maximum furnace heat release will not exceed 370,000 B.T.U's per square foot of area, 11 feet per second; (4) Flue cross section area not less than one square foot for each 850,000 Btu's released in the furnace, 25 feet per second; (5) Chimney cross section area not less than one square foot per 780,000 Btu's of heat released in the furnace based on an assumed 50- to 60-foot stack. The equivalent velocity is about 23 feet per second; (6) Calculation for combustion air shall be: Btu × 7.6 10,000 based on figuring zero excess air; (7) Calculations to include provision for 50 percent excess air; (8) Total weight of products of combustion shall equal total combustion air plus 90 percent of dry fuel; (9) Design of incinerator and its equipment for the disposition of moisture in the fuel shall also include computation of the volumes for the control of velocities, including the volume of superheated steam at the design unit temperature, plus the volume of the products of combustion; (10) In the case of steel stack a painter trolley shall also be provided. (Ord. No. 81-73, § 3.2-E, 11-4-81)
Ask a question about Dearborn law
Corpus searches the Dearborn sections it holds and shows the ones that match, with their citations. Free, no sign-in.