§ 13-157 — - Furnace volume
Code of Ordinances of the City of Dearborn, Michigan (2026 S-07: Code and Zoning updated through September 22, 2026) · Dearborn City Code § 13-157
Corpus is an independent public-information project, not the official City of Dearborn website. Stable reference: corpuslaw.us/code/3651f5e8-f150-4c08-855e-2a5435be2ec9
Sec. 13-157. - Furnace volume.
Requirements for furnace volume shall be as follows: (1) A steam boiler furnace or other furnace using hand-method of firing shall be provided with a furnace volume of not less than one cubic foot combustion volume for each rated horsepower, or for each 140 square feet equivalent direct radiation capacity. (2) Mechanical stokers shall be provided with a furnace volume of not less than one cubic foot per rated horsepower. (3) Furnaces using fuel oil shall be provided with a furnace volume of not less than 1.50 cubic feet per rated horsepower, or for each 140 square feet equivalent direct radiation. (4) Furnaces using pulverized coal shall not have less than three cubic feet furnace volume per rated horsepower. (5) Wood-refuse burning boilers or furnaces shall maintain a furnace volume of from six to ten cubic feet per rated horsepower. (6) Refuse-burners and destructor type of incinerators shall maintain a furnace volume of two cubic feet per square foot grate surface. (Ord. No. 81-73, § 3.6, 11-4-81)