Sec. 19-100. - Same - Acceptable devices.
Only the devices indicated below are acceptable for protection against backflow: (1) An approved air gap at the customer service for protection of the public water system. (2) An air gap on the premise piping system only when specifically authorized by the authority. (3) A reduced pressure principle backflow preventor for all backflow protection conditions, except at a service to a waste treatment plant. (4) A double check valve assembly for an automatic fire sprinkler system using an anti-freeze solution approved by the authority; and for the following specified use: a. A low pressure boiler not subject to chemical treatment. b. A closed recirculating system used for heating and cooling not subject to chemical treatment. c. A water softener of the automatically regenerative type. (5) A barometric loop for a water connection not subject to back pressure. (6) A vacuum breaker for water connections not subject to back pressure, such as standard plumbing fixtures, lavatory sinks, lawn irrigation systems, and those submerged inlets specifically authorized by the authority. (Ord. No. 81-12, § 16.4, 1-20-81)