Sec. 19-103. - Air gaps.
Safe air gap shall be maintained between the water supply inlet and the maximum overflow level of any fixture, tank, or container. Safe air gaps shall be determined as follows: (1) Circular openings. Circular water supply inlet openings shall have an air gap equivalent to twice the diameter of the orifice; but not less than one inch and need not be more than 12 inches. (2) Other openings. For water supply openings other than circular, the air gap shall be 2¼ times the square root of the area of the opening. (3) Equations. Or in equation form: G = 2d for circular openings, G = 2 - ¼ square root A for other openings, where G = the air gap, D = the diameter and A = the area. (4) Exceptions. On openings greater than four-inch diameter or of equivalent area, if the opening is other than circular, the authority shall be consulted for minimum air gaps. (Ord. No. 81-12, § 16.8, 1-20-81)