Sec. 19-101. - Vacuum breakers.

(a) Any atmospheric type vacuum breaker shall be installed on the discharge side of the last control valve and, on open vessels, shall be at least six inches above the flood level rim of the device; or at a distance equal to the critical level, plus such safety factor as may be specified for any given vacuum breaker by the authority. For closed vessels the top of the device shall be treated as the flood level rim, but, in addition, a check valve shall be installed on the discharge side of the vacuum breaker. (b) Pressure type vacuum breakers may be installed so that they are continuously subject to static line pressure. Pressure vacuum breakers shall be installed a minimum of 12 inches above the equipment or piping served, whichever is higher. (Ord. No. 81-12, §§ 16.5, 16.6, 1-20-81)