Sec. 19-108. - Automatic fire sprinkler systems.
(a) Where necessary to provide an automatic fire sprinkler system using antifreeze solutions to serve an unheated area, only antifreeze approved by the authority may be used. Such systems shall have not more than 20 heads and shall have at all times prominently posted, within two feet of the fill location, a warning sign at least eight inches by ten inches in size, having letters of one inch in height, bearing the following statement: "USE ONLY MATERIALS AUTHORIZED BY THE CITY OF DEARBORN." (b) Signs are to be furnished and maintained by the owner and must be of materials and design acceptable to the director. (c) In the supply line to each antifreeze system, there shall be a RPZ installed in the supply piping. (d) When requested in writing by an owner, occupant of lessee, the authority may permit use of antifreeze solutions not approved by the authority, provided a reduced pressure principle backflow preventor is installed at the connection to the potable water system. (Ord. No. 81-12, §§ 16.17-16.22, 1-20-81; Ord. No. 2020-1689, 10-20-20)