§ 5-1267 — - Service entrance conductors
Code of Ordinances of the City of Dearborn, Michigan (2026 S-07: Code and Zoning updated through September 22, 2026) · Dearborn City Code § 5-1267
Corpus is an independent public-information project, not the official City of Dearborn website. Stable reference: corpuslaw.us/code/f7e175dd-a679-4f90-8517-f9f50ef9cf74
Sec. 5-1267. - Service entrance conductors.
(a) Overhead. Overhead service entrance conductors on or in all buildings of other than single and up to and including four-family dwellings shall be installed in rigid conduit, electrical metallic tubing or busway, or other similar approved means. A minimum vertical clearance abovegrade shall be 12 feet for service drop conductors to all buildings used for other than residential purposes. For single and two-family services, see article 230 section 24. Service entrance cables extended horizontally along the exterior of building shall be supported at least every three feet. Horizontal runs adjacent to alleys or driveways shall be elevated at least eight feet abovegrade. Service cable shall be equipped with service cable weatherhead above point of attachment. (1) Service entrance conductors underground shall have a depth of not less than 30 inches measured from present surface of ground or final grade, whichever is lower. Conductors entering a building shall be protected to the point of entrance. Where the enclosure or raceway is subject to physical damage, the conductors shall be installed in rigid metal conduit, schedule 80 rigid P.V.C. (2) Service drops, supports or brackets shall not be attached to chimneys or to fire or parapet walls extending above the roofline. A suitable support shall be provided at all locations. (b) Temporary service. All outdoor temporary service equipment must be enclosed in a raintight enclosure or equipment approved for outdoor use with suitable provision for locking. One-hundred- twenty-five volt, single-phase 15 or 20 ampere receptacles shall have ground-fault circuit-interrupter protection for personnel. (c) Location. Service equipment shall not be located in coal bins, bathrooms, lavatories or clothes closets. Where practicable, it should be located in the basement or utility room. If installed in a finished wall in the living area, it is recommended that provisions be made for addition of extra circuits when reserve capacity exists. Recessing panelboards into plastered walls or totally enclosed panelboards shall be avoided; accessibility and working space are very necessary to provide easy access for maintenance, circuit additions and heat transfer. In single- and two-family dwellings, this equipment shall be at least four feet from the deck grade, shall not be subject to mechanical injury or shall be provided with suitable protection. Sufficient clearance and accessibility shall be provided when installed in basement near laundry trays, oil tanks, or other permanently installed obstructions. (d) Dead front requirement. Direct current 0-30 ampere and single phase 0-125 ampere service equipment shall be dead front in residential occupancies up to and including four-family occupancies and shall be designated service equipment or suitable for use as service entrance equipment. Dead front equipment is equipment having no live parts exposed whereby accidental contact may be made. (e) Two hundred ampere service. Consult local inspection authority when service equipment is 200 ampere or larger. (Ord. No. 91-511, § 6.3, 2-13-91)
Ask a question about Dearborn law
Corpus searches the Dearborn sections it holds and shows the ones that match, with their citations. Free, no sign-in.