Sec. 5-1284. - Temporary light and power facilities.
(a) Where electric lighting for temporary barricades is used, it shall be on independent circuits and arranged to burn continuously, lamps shall be protected by suitable guards or by elevation. (b) Branch circuits for construction purposes supplying energy for temporary light and power outlets shall be not smaller than No. 12 A.W.G. for distances less than 125 feet from source of supply. Circuits in excess of 125 feet shall be not less than No. 10 A.W.G. Receptacles shall be 125 volt, single phase, 15 or 20 ampere, and it shall have ground-fault circuit-interrupter protection for personnel; not more than four such outlets per circuit. Lighting outlets shall be limited to eight per circuit. (Ord. No. 91-511, § 6.20, 2-13-91)