§ 5-995 — - Tank vents
Code of Ordinances of the City of Dearborn, Michigan (2026 S-07: Code and Zoning updated through September 22, 2026) · Dearborn City Code § 5-995
Corpus is an independent public-information project, not the official City of Dearborn website. Stable reference: corpuslaw.us/code/7f7cb344-f041-47aa-9935-a7f289f70383
Sec. 5-995. - Tank vents.
Storage tanks shall be equipped with an open vent or an approved automatically operated vent, arranged to discharge to the open air. Vent openings and vent pipes shall be of ample size to prevent abnormal pressure in the tank during filling but not smaller than three-fourths-inch pipe size for tanks up to 500-gallon capacity; one-inch pipe for tanks up to 1,000. The vent from oil tanks shall be increased one-half inch in diameter for each 1,000 gallon capacity on oil tanks over 1,000 gallons in size. (Ord. No. 81-65, § 10.30, 11-4-81)
Ask a question about Dearborn law
Corpus searches the Dearborn sections it holds and shows the ones that match, with their citations. Free, no sign-in.