Sec. 5-986. - Same - Installation specifications.
(a) Oil supply tanks located inside buildings shall not exceed 275 gallons individual capacity or 550 gallons aggregate capacity, in one building, unless installed in an enclosure or casing constructed as follows: (1) The walls of the enclosure shall be constructed of reinforced concrete at least six inches thick or of brick at least eight inches thick, and shall be bonded to the floor. The space between the tank and the enclosure shall be completely filled with sand or well tamped earth. (2) Where the floor or other construction immediately above the tank is of fire-resistive construction capable of safely sustaining a load of 150 pounds per square foot, the walls of the enclosure shall be carried to a height not less than one foot above the tank and the space filled with sand or well tamped earth to the top; otherwise, the enclosure shall have a top of reinforced concrete at least five inches thick or of equivalent construction. (b) Instead of an enclosure as above described, the tank may be encased in reinforced concrete not less than six inches in thickness, applied directly to the tank so as to completely eliminate any air space. (Ord. No. 81-65, § 10.21, 11-4-81)