Sec. 5-977. - Supply tanks capacity.
(a) Gravity supply tanks shall not exceed 275 gallons individual capacity. Where more than one gravity supply tank is used, such tanks shall be connected to the feed pipe leading to the burner through a manually operated, approved three-way valve in such a way that only one tank can discharge its contents at one time. (b) On multiple tank installations, the fill pipe shall be so arranged that both tanks will fill equally, and the vent pipe shall extend well above cross connections between tanks to prevent air binding when filling. (Ord. No. 81-65, § 10.12, 11-4-81)