§ 5-990 — - Construction - Capacity
Code of Ordinances of the City of Dearborn, Michigan (2026 S-07: Code and Zoning updated through September 22, 2026) · Dearborn City Code § 5-990
Corpus is an independent public-information project, not the official City of Dearborn website. Stable reference: corpuslaw.us/code/c6ec6845-7a17-47fd-8088-26b1e11d0953
Sec. 5-990. - Construction - Capacity.
(a) Underground tanks and tanks inside buildings shall be constructed of steel or wrought iron of a minimum gauge (U.S. Standard) in accordance with the following table, except that for tanks of 181 to 275 gallons capacity, installed in buildings, and without masonry enclosures, the minimum gauge shall be No. 14 steel, or wrought iron thinner than No. 7 gauge used in the construction of underground and enclosed tanks shall be galvanized. Capacity, Gals. | Minimum Thickness | Weight Lbs. per Sq. Ft. 7 to 275 | 16 gauge | 2.50 276 to 560 | 14 gauge | 3.125 561 to 1,100 | 12 gauge | 4.375 1,101 to 4,000 | 7 gauge | 7.50 4,001 to 12,000 | ¼ in. (nom) | 10.00 12,001 to 20,000 | 5/16 in. (nom) | 12.50 20,001 to 30,000 | 3/8 in. (nom) | 15.00 (b) If adequate internal bracing is provided, tanks of 12,001 to 30,000 gallons capacity may be built of one-fourth-inch plate; for tanks larger than 1,100 gallons capacity, having adequate internal bracing, a tolerance of ten percent incapacity is permitted. (Ord. No. 81-65, § 10.25, 11-4-81)
Ask a question about Dearborn law
Corpus searches the Dearborn sections it holds and shows the ones that match, with their citations. Free, no sign-in.