Sec. 5-980. - Underground tanks - Installation.

Underground tanks shall be so buried as to have a cover of earth not less than two feet thick, or shall be covered with not less than one foot of earth on top of which shall be placed a slab of reinforced concrete not less than four inches thick. The slab shall be set on a firm, well tamped earth foundation and shall extend at least one foot beyond the tank in all directions. Where tanks are buried underneath buildings, such a concrete slab shall be provided in every instance. (Ord. No. 81-65, § 10.15, 11-4-81)