§ 5-979 — - Pressure feed
Code of Ordinances of the City of Dearborn, Michigan (2026 S-07: Code and Zoning updated through September 22, 2026) · Dearborn City Code § 5-979
Corpus is an independent public-information project, not the official City of Dearborn website. Stable reference: corpuslaw.us/code/96cca896-186f-49f3-8362-214e3e2b2b6b
Sec. 5-979. - Pressure feed.
(a) Pressure tank feed shall be used only with burners arranged to prevent abnormal discharge of oil at the burner by automatic means specifically approved for the burner with which it is used. (b) Pressure tanks shall not exceed a capacity of 60 gallons, and shall not be operated at pressures exceeding 50 pounds per square inch. They shall be equipped with a reliable pressure gauge, approved by the A.S.M.E., and with an automatic relief valve piped to discharge outside of buildings. (Ord. No. 81-65, § 10.14, 11-4-81)
Ask a question about Dearborn law
Corpus searches the Dearborn sections it holds and shows the ones that match, with their citations. Free, no sign-in.