25.12.163 General; Amended.

Section 304 (IFGS) Combustion, Ventilation and Dilution Air Section 304.1 of the International Fuel Gas Code is amended to read as follows: Air handling systems or ducting installed in newly constructed residences shall bring in outside air for combustion/ventilation air when open combustion heating appliances, water heaters, boilers, or open faced gas fireplaces are installed. The outside air shall be 4 inch minimum round but not less than 50% of the flue size serving such appliances. The outside air may be ran in insulated class 0 or 1 flexible duct but must terminate with galvanized metal within 6 feet of the appliance served or into the return air system at a point where interior air is directly mingled with the outside air. Hoods serving outside air ducts must be installed 12 inches minimum above grade.

(Ord. 20528 §18, August 21, 2017)