25.12.215 Section 503.3.6 Amended; Above Ceiling Air Handling Spaces.
Section 503.3.6 of the 2021 International Fuel Gas Code is amended to read as follows: Where a venting system passes through an above-ceiling air-handling space or other nonducted portion of an air handling system, the venting system shall conform to one of the following requirements: (1) 1. The venting system shall be a listed special gas vent; other venting system serving a Category III or Category IV appliance; or other positive pressure vent, with joints sealed in accordance with the appliance or vent manufacturer’s instructions. No joints may be in the return air space even if covered with insulation material. (2) 2. The venting system shall be installed such that fittings or joints between sections are not installed in the above-ceiling space. (3) 3. The venting system shall be installed in a conduit or enclosure with sealed joints separating the interior of the conduit or enclosure from the ceiling space. (: Ord. 20528 §28, August 21, 2017).
(Ord. 21816 §24; December 15, 2025; Ord. 21114 §14; August 23, 2021)