Code of the City of Arlington, Texas (City Secretary chapter PDFs as posted 2026-11-07, each current through the ordinance named on its cover, with the City Secretary's adopted-not-yet-codified Ordinances 25-063, 25-069, 25-073, 25-074, 25-075, 25-084, 26-003, 26-004, 26-019, 26-024 and 26-027 applied; Anti-Discrimination chapter not included) · Arlington City Code, Backflow Prevention Chapter, § 2.02

Corpus is an independent public-information project, not the official City of Arlington website. Stable reference: corpuslaw.us/code/e1445a58-ad98-4e83-a9ee-4cecc46a650a

Section 2.02 Installation Requirements

A. Backflow prevention assemblies shall be installed in accordance with the following requirements: 1. Backflow prevention assemblies shall be installed in accordance with the Plumbing Code, Commission rules, this Chapter, and other relevant law. The assembly installer shall obtain the required plumbing permits prior to installation and shall have the assembly inspected by the Regulatory Authority. 2. When the Regulatory Authority requires a backflow prevention assembly to be installed at the point of delivery of both potable and reclaimed water supplies, such installation of the assembly shall be before any branch in the line and on private property located just inside the boundary between the City right-of-way and the landowner's property. Other areas of installation of a backflow prevention assembly may be required when the Regulatory Authority deems it necessary in order to protect the water supply of the City from contamination or pollution. 3. The assembly shall be protected from freezing and other severe weather conditions. 4. All backflow prevention assemblies shall be of a type and model approved by the Regulatory Authority. 5. Vertical installations of backflow prevention assemblies shall be approved in writing by the Regulatory Authority prior to installation. 6. Backflow prevention assemblies that are larger than four (4) inches and are installed more than five (5) feet or higher above floor level shall be equipped with a rigidly and permanently installed scaffolding acceptable to the Regulatory Authority. 7. Bypass lines are prohibited. Pipe fittings which could be used for connecting a bypass line shall not be installed. 8. Premises that require backflow prevention assemblies, where an uninterrupted, continuous water supply is critical shall be provided with two (2) assemblies installed in parallel for testing, maintenance, or repair. They should be sized in such a manner that either assembly will provide the maximum flow required or desired. 9. Lines shall be thoroughly flushed prior to installation. A strainer with blowout tapping may be required ahead of the backflow prevention assembly. 10. Upon completion of installation, the Regulatory Authority shall be notified and all backflow prevention assemblies shall be inspected and tested. The original test report shall be: signed and dated by the tester; contain test gauge make, model, serial number, and calibration date; name of tester; state certification number of tester; facility name, address and telephone number; and, submitted to the Regulatory Authority. B. A person commits an offense if the person installs a backflow prevention assembly in violation of this section. C. A person commits an offense if the person fails to notify the Regulatory Authority of installation, to inspect and test, or to report the test report in compliance with this Chapter.

(Amend Ord 11- 018, 3/22/11)

Ask a question about Arlington law

Corpus searches the Arlington sections it holds and shows the ones that match, with their citations. Free, no sign-in.