§ 2.02.155 — Amendment to IBC Section 1010.1.9.4 – Locks and Latches by addition of item 11
Municipal Code, City of Tacoma, Washington (Tacoma Municipal Code current through legislation adopted 2026-09-30 (eCode360 publication TA6977, scraped 2026-11-18)) · Tacoma Municipal Code § 2.02.155
Corpus is an independent public-information project, not the official City of Tacoma website. Stable reference: corpuslaw.us/code/9f98304b-aeed-497a-bea6-632fe6500bcf
§ 2.02.155: Amendment to IBC Section 1010.1.9.4 – Locks and Latches by addition of item 11.
11. Doors from elevator lobbies providing access to exits are permitted to be locked during or after business hours where items 11.1 through 11.6 are satisfied. 11.1. The lobby doors shall unlock automatically upon fire alarm; 11.2. The lobby doors shall unlock automatically upon power loss; 11.3. The alarm system shall include smoke detection in the elevator lobby and at least two detectors on the tenant side within 15 feet of the door; 11.4. Unobstructed access to two exits must be provided through the tenant space; 11.5. The building shall have an automatic sprinkler system throughout in accordance with Section 903.3.1.1 or 903.3.1.2; and 11.6. An approved means of communication is provided in the elevator lobby.
( Ord. 28590 Ex. A, 2019-06-18 ; Ord. 28729 Ex. A, 2021-01-26 ; Ord. 28957 Ex. A, 2024-03-05 )