Sec. 18-230. - Same—Lintels and arches.

All openings in masonry walls shall be spanned by plain or reinforced arches, steel lintels or other approved noncombustible supports with not less than four-inch bearing on the wall at each end. Plain stone lintels shall not be used on spans greater than four feet nor to support load concentrations on the wall less than two feet above the top of the lintel unless supplemented by structural lintels or arches. All lintels shall be of sufficient strength to support the superimposed load with a deflection of not more than 1/360 of clear span, and arches shall be designed to support the load with provision to resist the lateral thrust.

(Code 1973, § 30.26.010)