§ 18-28-1105.5 — Refrigerant detector
Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 18-28-1105.5
Corpus is an independent public-information project, not the official City of Chicago website. Stable reference: corpuslaw.us/code/2165d275-39f0-4cf0-b9b9-6eed38c73027
18-28-1105.5 Refrigerant detector.
Machinery rooms shall contain a refrigerant detector with an audible and visual alarm. The detector, or a sampling tube that draws air to the detector, shall be located in an area where refrigerant from a leak will concentrate. The alarm shall be actuated at a value not greater than the corresponding TLV-TWA valves shown in Table 18-28-1103.1. Audible alarm(s) shall be placed directly outside of the machinery room. Visual alarm(s) shall consist of a flashing yellow light placed directly over the machinery room door(s) with a sign that states: DANGER DO NOT ENTER WHEN LIGHT IS FLASHING PELIGRO NO ENTRAR CUANDO LA LUZ ESTE PARPADEANDO (Amend Coun. J. 9-14-21, p. 35949, Art. XI, § 10)
Ask a question about Chicago law
Corpus searches the Chicago sections it holds and shows the ones that match, with their citations. Free, no sign-in.
