18-28-1105.5 Refrigerant detector.

Machinery rooms shall contain a refrigerant detector with an audible and visual alarm. The detector, or a sampling tube that draws air to the detector, shall be located in an area where refrigerant from a leak will concentrate. The alarm shall be actuated at a value not greater than the corresponding TLV-TWA valves shown in Table 18-28-1103.1. Audible alarm(s) shall be placed directly outside of the machinery room. Visual alarm(s) shall consist of a flashing yellow light placed directly over the machinery room door(s) with a sign that states: DANGER DO NOT ENTER WHEN LIGHT IS FLASHING PELIGRO NO ENTRAR CUANDO LA LUZ ESTE PARPADEANDO (Amend Coun. J. 9-14-21, p. 35949, Art. XI, § 10)