17.12.1005 - Amendment of Chapter 80 - NFPA 13-25 - Standard for the Installation of Sprinkler Systems.
The following sections of NFPA 13 - 25 edition, Standard for the Installation of Sprinkler Systems, are amended to read as follows:
Section 9.2.1 is amended to delete the following sections:
9.2.1.1, 9.2.1.2, 9.2.1.10, 9.2.1.12, 9.2.1.13. 9.2.1.14, 9.2.1.18, and 9.2.1.19.
Section 11.1 is amended to read as follows:
11.1.1 The use of extended coverage sprinklers shall require prior approval from the San José Fire Department.
Section 16.9.3 is amended to read as follows:
16.9.3.6 Fire sprinkler system risers or control valves shall not be located in electrical rooms.
Section 16.9.10 is amended to read as follows:
16.9.10.1 Multistory buildings exceeding one story in height shall be provided with a floor control valve, check valve, pressure gauge, main drain valve, and flow switch for isolation, control, and annunciation of water flow for each individual floor level.
16.9.10.2 is deleted.
16.9.10.3 is deleted.
16.9.10.4 is deleted.
Section 19.2.3.2 is amended to read as follows:
19.2.3.2.3 is deleted.
19.2.3.2.9 For light hazard areas designated for office use, one-inch plugged, threaded outlets shall be provided at each sprinkler. The minimum flow at each sprinkler shall be not less than 0.10 gpm/square feet, with a minimum design area of three thousand (3,000) square feet or equivalent as approved by the fire code official. Only standard spray sprinklers shall be used. Extended coverage sprinkler heads shall not be used.
19.2.3.2.10 When a fire sprinkler system is required in a building of undetermined use with roof height of twenty feet (20') or less, it shall be installed for an ordinary hazard occupancy with a minimum design density of not less than 0.20 gpm/square feet, with a minimum design area of three thousand (3,000) square feet. The system demand, including 250 gpm hose stream allowance, shall be designed at a minimum of ten percent below the available water supply. One-inch plugged, threaded outlets shall be provided at each sprinkler. Where a subsequent occupancy requires a system with greater capability, it shall be the responsibility of the owner and/or occupant to upgrade the system. Provided no current or future High-Pile Storage as indicated by a letter from the property owner embedded on the submitted plans. If such a letter is not provided, the design shall be per Section 19.2.3.2.11.
19.2.3.2.11 When a fire sprinkler system is required in a building of undetermined use with floor to roof height greater than twenty feet (20'), a fire sprinkler system, for the building shell, shall be designed to incorporate Commodity Class IV storage hazard based on the roof height in accordance with NFPA 13 Chapter 21 or equivalent as approved by the fire code official (such as ESFR). The system demand, including 500 gpm hose stream allowance, shall be designed at a minimum of ten percent below the available water supply. One-inch plugged, threaded outlets shall be provided at each sprinkler. Where a subsequent occupancy requires a system with greater capability, it shall be the responsibility of the owner and/or occupant to upgrade the system.
Section 28.2 of NFPA 13 - 25 edition is amended to read as follows:
28.2.1.7 The safety margin for hydraulic calculations shall be a minimum 10% of the water supply data.
28.2.4.13 The maximum water velocity in the hydraulic calculations shall be twenty feet per second (20 ft/sec) when designing to the criteria as set forth herein as Sections 19.2.3.2.9, 19.2.3.2.10, and 19.2.3.2.11.