11.79.490 - Spas.
A spa is a bathing pool designed for non-swimming recreational use. It may include, but is not limited to, hydrojet circulation, hot water, mineral baths, air induction systems, or any combinations thereof.
A. Maximum Depths. The maximum water depth shall be four (4) feet measured from the water line. The maximum submerged depth of any seat or sitting bench shall be two (2) feet measured from the water line.
B. Handholds. A spa shall have one (1) or more suitable, slip-resistant handhold(s) around the perimeter, located no farther apart than four (4) feet and not over twelve (12) inches above the water line.
C. Stairs, Ladders and Recessed Treads. Stairs, ladders or recessed treads shall be provided where spa depths are greater than two (2) feet. A spa shall be equipped with at least one means of egress with a handrail for each fifty (50) feet of perimeter or portion thereof.
D. Deck Widths. A five (5) foot minimum width, continuous, unobstructed deck, which may include the coping, shall be provided on two (2) sides or fifty percent or more of the spa perimeter. When the spa is adjacent to another pool, the spa shall be located at the shallow end with a minimum distance of five (5) feet between the pools. Spas constructed and operated prior to the effective date of this chapter shall be exempted, provided they comply with the minimum sanitary and safety requirements adopted herein.
E. Water Temperature Controls. Controls shall be provided to prevent water temperatures in excess of 105ºF. The controls shall be accessible only to the pool operator.
F. Spa Drainage. Means to drain the spa shall be provided to allow frequent draining and cleaning.
G. Entrapment Protection. Outlets shall be designed so that each pumping system prevents patron entrapment. Acceptable means include the use of multiple unvalved outlets, an anti-vortex drain, and a twelve (12) inch by twelve (12) inch square grate or one of equivalent area.
H. Surface Skimmers. One surface skimmer shall be provided for each one hundred (100) square feet or major fraction thereof of surface area.
I. Inlets. One (1) wall inlet shall be provided for each twenty (20) feet of pool perimeter, and a minimum of two (2) wall inlets shall be provided.
J. Air Induction Systems. An air induction system, when provided, shall prevent water back-up that could cause electrical shock hazards.
K. Disinfection. An approved sanitizer is required. If chlorine compounds are used for disinfection, a free residual between 1 ppm and 3 ppm shall be maintained throughout the spa. Gas chlorinators shall not be used. A pH level of 7.2 to 7.8 shall be maintained. All disinfection equipment shall be National Sanitation Foundation-approved. Manual addition of chemicals as authorized by the Commissioner may be allowed if the spa is closed.
L. Recirculation Flow Rates. The recirculation flow rate shall be thirty (30) gallons per minute per skimmer or provide a thirty (30) minute turnover, whichever is greater.
M. Agitation Systems. The agitation system shall be separate from the water treatment recirculation system. The agitation system shall be connected to a ten (10) minute timer located out of the reach of a person in the spa.
N. Caution Signs. A sign visible and legible from the spa shall be provided. It shall state: "Caution. Any person having an acute or chronic medical condition such that use of this spa might adversely affect their health should consult a physician before using this spa. Do not use the spa immediately following exercise or while under the influence of alcohol. Do not use the spa longer than ten (10) minutes. Children shall be accompanied by an adult."
O. Operation. Spas constructed or operated prior to the effective date of this section, which do not fully comply with the minimum requirements regarding the design and construction, may be continued in use, provided the equipment and operation of such spas comply with the minimum sanitary and safety requirements adopted herein.
(1994 C., § 11.79.490; Ord. No. 65567, § 49, 2002.)