§ 18-28-1106.12 — Hand-operated emergency valves

Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 18-28-1106.12

Corpus is an independent public-information project, not the official City of Chicago website. Stable reference: corpuslaw.us/code/b8117080-fefa-4d81-8de0-7d7316fee941

18-28-1106.12 Hand-operated emergency valves.

All Direct Expansion Refrigeration Systems containing more than 100 pounds (45.36 kg) of refrigerant shall be provided with a hand operated emergency valve. Such device shall be connected to the low side of the refrigeration system and be located where the emergency valve is readily available for Fire Department use. Valves shall be identified and operating instructions for the use of the emergency valve shall be provided at the location of the valve. Hand operated emergency valves shall be of the following sizes and a maximum inlet pipe length of one hundred (100) feet (30.48 m): Pounds of Refrigerant in System | Valve Size 100 – 200 | 1 inch nominal pipe size 201 – 300 | 1 1/4 inches nominal pipe size 301 – 500 | 1 1/2 inches nominal pipe size 501 – 1,000 | 2 inches nominal pipe size above 1,000 | 3 inches nominal pipe size