§ 15.30.250 — Prescriptive design—Sill plates
Oakland Municipal Code (Supp. No. 103: codified through Ordinance No. 13873, adopted February 17, 2026) · Oakland Municipal Code § 15.30.250
Corpus is an independent public-information project, not the official City of Oakland website. Stable reference: corpuslaw.us/code/71c1023f-2c9b-472f-ba9c-570960e11b38
15.30.250 - Prescriptive design—Sill plates.
A. Connection. Sill plates shall be connected to foundations in accordance with the Oakland Building Construction Code, or as otherwise approved by the Building Official. Anchors within braced panels of cripple walls shall be spaced apart not more than thirty-two (32) inches (two-anchors minimum per continuous sill plate). Sill plates shall be drilled for fasteners used with anchor side plates before installation. B. Anchors. Adhesive and expansion anchors shall be installed with a metal plate washer between the nut and the sill plate or supplemental block. Washers shall be 2-inch × 2-inch × 3/16 -inch. Expansion anchors shall not be used in assembled masonry or unreinforced concrete foundations. Adhesive anchors shall be used where expansion anchors cause surface cracking of the foundation or cannot be tightened as required by the manufacturer's recommendations. Supplemental blocks for through-anchor installation, when installed, shall be two-inch nominal thickness lumber and fastened to sill plates with not less than four 10d common nails.
(Ord. 12812 § 1 (part), 2007)