§ 15.30.270 — Prescriptive design—Cripple walls
Oakland Municipal Code (Supp. No. 103: codified through Ordinance No. 13873, adopted February 17, 2026) · Oakland Municipal Code § 15.30.270
Corpus is an independent public-information project, not the official City of Oakland website. Stable reference: corpuslaw.us/code/1db1f984-4c6b-4751-9980-a8ecd2137bd9
15.30.270 - Prescriptive design—Cripple walls.
A. Bracing. 1. Cripple walls shall be braced with exterior grade structural wood panel sheathing not less than 15/32 -inch thickness. Plywood sheathing shall be not less than five plies. 2. Sheathing shall be fastened to cripple wall studs, top plate, and sill plate. Fasteners shall be 8d common nails spaced apart not more than four inches at sheathing edges and not more than twelve inches at intermediate supports and shall be installed not less than 3/8-inch from sheathing edges. 3. Sheathing horizontal joints shall be continuously supported between studs by full-width and full-depth, two-inch nominal thickness lumber blocking. Sheathing vertical joints shall continuously supported by stud framing. 4. Supplemental studs ("sistered") shall be full-depth and full-height and fastened to existing studs with 16d common nails spaced apart not more than eight inches in a vertically staggered pattern (three nails minimum). 5. Top plates shall be lapped and fastened in accordance with the Oakland Building Construction Code or spliced with an equivalent supplemental connector installed on the sheathing face. 6. Supplemental blocking for sheathing bottom edge-nailing shall be full-width and full-depth between studs, twice nominal thickness lumber, and fastened to sill plates with 10d common nails spaced apart not more than six inches in an alternating pattern (four nails minimum). 7. Cutouts in sheathing and notches in top plates, sill plates, and existing studs for obstructions (piping, underfloor ventilation and access, ducts, etc.) shall be reinforced with supplemental connectors and approved by the Building Official. B. Bracing Distribution. 1. Braced End-Panels. Cripple walls shall be braced at each end of the wall line, or elsewhere along the wall line when approved by the Building Official. The horizontal length of a braced end-panel shall be not less than eight feet, measured at any point. 2. Braced Intermediate-Panels. Cripple walls also may be braced with intermediate-panels spaced apart evenly between braced end-panels. The horizontal length of an intermediate-panel shall be not less than four feet, measured at any point, and not less than twice the vertical height of the braced panel for buildings with tile roofing or with portland cement plaster or brick or stone veneer exterior building surfaces. 3. Unbraced Sections. Cripple walls may have unbraced sections between braced panels. The horizontal length of an unbraced section of wall line shall be a. not more than sixteen (16) feet, measured at any point, for a one-story building with wood exterior building surfaces, and b. not more than twelve (12) feet, measured at any point, for a one-story building with tile roofing or with portland cement plaster or brick or stone veneer exterior building surfaces, and c. not more than eight feet, measured at any point, for two story buildings with tile roofing or with portland cement plaster or brick or stone veneer exterior building surfaces. C. Ventilation. 1. Underfloor ventilation shall not be reduced. 2. Sheathed stud cavities shall be individually ventilated with two-inch diameter holes drilled through the bracing sheathing, and centered within the stud cavity, and located not less than one inch below the top plate, and one inch above the sill plate, and one inch above and below horizontal blocking. Cavities with stud height less than eighteen (18) inches shall have a single ventilation hole.
(Ord. 12812 § 1 (part), 2007)
Ask a question about Oakland law
Corpus searches the Oakland sections it holds and shows the ones that match, with their citations. Free, no sign-in.