§ 85.2.160 — Appendix B and Bb - Fire Flow Requirements for Buildings. [Climatic, Geological, Topographical]
Municipal Code, City of Torrance, California · Torrance Municipal Code § 85.2.160
Corpus is an independent public-information project, not the official City of Torrance website. Stable reference: corpuslaw.us/code/0334f171-b883-4bb0-a42b-23ea8bf6bec3
§ 85.2.160: Appendix B and Bb - Fire Flow Requirements for Buildings. [Climatic, Geological, Topographical]
Section B105.2 of Appendix B of the California Fire Code shall be amended to read in its entirety as follows: B105.2 Buildings other than One- and Two-Family Dwellings. The minimum fire flow and flow duration for buildings other than one and two-family dwellings shall be as specified in Table B105.1. Exception: A reduction in required fire flow of up to 50 percent, as approved is allowed when the building is provided with an approved automatic sprinkler system installed in accordance with Section 903.3.1.1, 903.3.1.2 or 903.3.1.3. The resulting fire flow shall not be less than 1,500 gallons per minute (5,677.5 L/min.) for the duration as specified in Table B105.1. Section BB105.2 of Appendix BB of the California Fire Code shall be amended to read in its entirety as follows: BB105.1 Buildings other than One- and Two-Family Dwellings. The minimum fire flow and flow duration for buildings other than one and two-family dwellings shall be as specified in Table BB105.1. Exception: A reduction in required fire flow of up to 50 percent, as approved is allowed when the building is provided with an approved automatic sprinkler system installed in accordance with Section 903.3.1.1, 903.3.1.2 or 903.3.1.3. The resulting fire flow shall not be less than 1,500 gallons per minute (5,677.5 L/min.) for the duration as specified in Table BB105.1.
Ask a question about Torrance law
Corpus searches the Torrance sections it holds and shows the ones that match, with their citations. Free, no sign-in.