Sec. 18-187. - IRC - Section R501.3.1, Structural floors ventilation.
Section R501.3.1. Structural floors ventilation, is hereby added to read as follows: "R501.3.1. Structural floor ventilation. Adequate under floor ventilation systems shall be provided to ventilate under floor areas when structural floor systems are required. Such systems shall be designed to provide at least one air change per hour, be controlled by a dehumidistat, and exhaust to the outside. A state licensed engineer's design may be required. Exception: The building official may approve alternates to such ventilation requirements when sufficient documentation is provided by the engineer of record to substantiate their alternate method is at least the equivalent of that prescribed."