Sec. 22-322. - Table 909.1 amended; maximum distance of fixture trap from vent.

Table 909.1 of the plumbing code shall be amended as follows: Table 909.1. Maximum Distance of Fixture Trap From Vent* Distance Trap to Vent Trap Arm Inches | Feet | Inches | Trap Arm mm | Distance Trap to Vent mm 1¼ | 2 | 6 | 32 | 762 1½ | 3 | 6 | 38 | 1,067 2 | 5 | 0 | 51 | 1,524 3 | 6 | 0 | 76 | 1,829 4 and larger | 10 | 0 | 102 and larger | 3,048 Slope = ¼ inch per foot (20.9 mm/m) *The developed length between the trap of a water closet or similar fixture (measured from the top of the closet ring [closet flange] to the inner edge of the vent) and its vent shall not exceed six feet.

(Code 1994, § 16.28.170; Ord. No. 47, 2016, §§ 1(exh. A), 2(exh. B), 12-20-2016)