Sec. 22-381. - Article 110.14(B), amended; splices.
Article 110.14(B) of the NEC © , adopted at section 22-377, is amended to read as follows: 110.14(B) Splices. Conductors shall be spliced or joined with splicing devices identified for the use or by brazing, welding, or soldering with a fusible metal or alloy. Soldered splices shall first be spliced or joined so as to be mechanically and electrically secure without solder and then be soldered. A listed oxide inhibitor compound shall be applied to all aluminum conductor splices per the manufacturer's installation instructions prior to splicing aluminum conductors with wing nuts, split bolts, or other approved devices. All splices and joints and the free ends of conductors shall be covered with an insulation equivalent to that of the conductors or with an identified insulation device. Wire connectors or splicing means installed on conductors for direct burial shall be listed for such use.
(Code 1994, § 16.32.050; Ord. No. 13, 2015, § 2, 6-2-2015)