Sec. 22-392. - Article 350.60, amended; grounding and bonding.
Article 350.60 of the NEC © , adopted at section 22-377, is amended to read as follows: 350.60 Grounding and bonding. Liquid-tight flexible metallic conduit shall not be permitted to be used as an equipment grounding conductor. An equipment grounding conductor shall be installed in all liquid-tight flexible metallic conduits and shall be installed in accordance with 250.134(B). Equipment bonding jumpers shall be installed in accordance with 250.102. FPN: See 501.30(B), 502.30(B), and 503.30(B) for types of equipment grounding conductors.
(Code 1994, § 16.32.160; Ord. No. 13, 2015, § 2, 6-2-2015)