§ 22-391 — Article 348.60, amended; grounding and bonding
Municipal Code of the City of Greeley, Colorado (Codified through Ordinance No. 16, 2026, enacted April 21, 2026 (Supp. No. 6, Update 1)) · Greeley Municipal Code § 22-391
Corpus is an independent public-information project, not the official City of Greeley website. Stable reference: corpuslaw.us/code/c49fb94e-2704-4088-9211-7b0508303f19
Sec. 22-391. - Article 348.60, amended; grounding and bonding.
Article 348.60 of the NEC © , adopted at section 22-377, is amended to read as follows: 348.60 Grounding and bonding. Flexible metallic conduit shall not be permitted to be used as an equipment grounding conductor. An equipment grounding conductor shall be installed in all flexible metallic conduits and shall be installed in accordance with 250.134(B). Equipment bonding jumpers shall be installed in accordance with 250.102.
(Code 1994, § 16.32.150; Ord. No. 13, 2015, § 2, 6-2-2015)
Ask a question about Greeley law
Corpus searches the Greeley sections it holds and shows the ones that match, with their citations. Free, no sign-in.
