Sec. 22-384. - Article 210.52(J) added; sump pit receptacle outlet.
Article 210.52(J) of the NEC © , adopted at section 22-377, is added to read as follows: 210.52(J) Sump pit receptacle outlets. A 125-volt, single-phase, 15- or 20-ampere receptacle outlet shall be installed adjacent to and within 18 inches of the sump pit. This receptacle outlet shall be on a dedicated branch circuit and shall be GFCI protected.
(Code 1994, § 16.32.090; Ord. No. 13, 2015, § 2, 6-2-2015)