Sec. 16.04.220. - Section 903.2.11.1 amended; specific building areas and hazards.

Section 903.2.11.1 of the International Building Code is amended by the addition of the following section: Section 903.2.11.1.4: Buildings greater than 12,000 square feet. An automatic sprinkler system shall be provided throughout all buildings where the fire area exceeds 12,000 square feet, or where the combined fire area on all floors, including mezzanines and basements, exceeds 24,000 square feet. Exception: This requirement shall not apply to buildings classified as Group F-2 occupancies.

(Ord. No. O-2026-23, § 1, 6-9-2026)