§ 16.04.270 — Section 905.2 replaced; installation standard
Code of Ordinances of the City of Longmont, Colorado (Codified through Ordinance No. O-2026-39, enacted June 23, 2026 (Supp. No. 9)) · Longmont Code of Ordinances § 16.04.270
Corpus is an independent public-information project, not the official City of Longmont website. Stable reference: corpuslaw.us/code/fd949303-3cd9-46b7-bf3d-659981e8e901
Sec. 16.04.270. - Section 905.2 replaced; installation standard.
Section 905.2 of the International Building Code is deleted in its entirety and replaced with the following: 905.2: Installation standard. Standpipe systems shall be installed/designed as an automatic wet standpipe with a 500 gpm at 100 psi at the two most demanding hose outlets in accordance with this section and NFPA 14. Fire department connections for standpipe systems shall be in accordance with section 912.
(Ord. No. O-2026-23, § 1, 6-9-2026)
Ask a question about Longmont law
Corpus searches the Longmont sections it holds and shows the ones that match, with their citations. Free, no sign-in.