§ 16.04.240 — Section 903.4.3 replaced; alarms

Code of Ordinances of the City of Longmont, Colorado (Codified through Ordinance No. O-2026-39, enacted June 23, 2026 (Supp. No. 9)) · Longmont Code of Ordinances § 16.04.240

Corpus is an independent public-information project, not the official City of Longmont website. Stable reference: corpuslaw.us/code/6ecfdcc7-99b7-4707-86fa-17ee2d53ee3c

Sec. 16.04.240. - Section 903.4.3 replaced; alarms.

Section 903.4.3 of the International Building Code is deleted in its entirety and replaced with the following: 903.4.3: Alarms. Approved audible/visual devices shall be connected to every automatic sprinkler system. Such sprinkler water-flow alarm devices shall be activated by water flow equivalent to the flow of a single sprinkler of the smallest orifice size installed in the system. An approved audible/visual sprinkler flow alarm shall be provided on the exterior of the building in an approved location above the fire department connection. An approved audible/visual sprinkler flow alarm to alert the occupants shall be provided throughout the interior of the building in accordance with sections 907.6 and NFPA 72. Where a fire alarm system is installed, actuation of the automatic sprinkler system shall actuate the building fire alarm system.

(Ord. No. O-2026-23, § 1, 6-9-2026)