Sec. 16.04.300. - Section 907.1.3 replaced; equipment.

Section 907.1.3 of the International Building Code is deleted in its entirety and replaced with the following: 907.1.3: Equipment. Systems and components shall be listed and approved for the purpose in which they are installed. Only addressable fire alarm panels will be approved. Exception: fire alarm panels that can transmit individual specific initiating device information. 907.1.3.1: Combination fire and security panels. A fire alarm system shall not be used for any purpose other than fire protection or control of fire protection systems. Combination fire and security panels are not permitted.

(Ord. No. O-2026-23, § 1, 6-9-2026)