8.36.040 - Burying of underground tanks.
Tanks buried underground shall have the top of the tank not less than two feet below the surface of the ground and below the level of any piping to which the tanks may be connected; except that, in lieu of the two-foot cover, tanks may be buried under twelve (12) inches of earth and a cover of reinforced concrete at least six inches in thickness provided, which shall extend at least one foot beyond the outline of the tank in all directions, such concrete cover to be placed on a firm, well-tamped earth foundation. Where necessary to prevent floating, tanks shall be securely anchored or weighted. Where a tank cannot be entirely buried, it shall be covered with earth to a depth of at least two feet with a slope on all sides not steeper than one and one-half feet horizontal to one food vertical.