§ 8.36.050 — Storage limits of underground tanks
Bridgeport, Connecticut Municipal Code (Supp. No. 24, Update 2: codified through Ordinance dated July 6, 2026) · Bridgeport Municipal Code § 8.36.050
Corpus is an independent public-information project, not the official City of Bridgeport website. Stable reference: corpuslaw.us/code/03099282-e998-48d4-853e-6d47f3d14d66
8.36.050 - Storage limits of underground tanks.
A. An underground tank for class I or class II flammable liquids shall be located not less than the distance indicated in the table set out in this section, measured horizontally from the nearest point of the shell to the nearest line of adjoining property that may be built upon and the nearest outside wall of any basement, pit or cellar of which the floor is lower in elevation than the top of such tank: Minimum Distance from Underground Tanks for Class I or II Flammable Liquids to Basements or to Line of Adjoining Property that May Be Built Upon Individual Tank Capacity Classes I and II (gallons) | Location If Top of Tank Is Above the Lowest Floor, Basement, Cellar or Part of Any Building Which Is Not Less Than: 550 ..... | 5 feet away 5,000 ..... | 10 feet away 10,000 ..... | 15 feet away 15,000 ..... | 20 feet away 25,000 ..... | 25 feet away. B. The location of the underground storage tank for class III shall not be less than two feet distant from property lines, basements, pits or cellars. All excavations for underground tanks shall be made with due care to avoid undermining of foundations of existing structures.
(Prior code § 11-60)
Ask a question about Bridgeport law