§ 7-110 — Burners firing 500,000 BTUs per hour or larger input

Code of Ordinances of the City of Cedar Falls, Iowa (Codified through Ordinance No. 3140, enacted March 16, 2026. (Supp. No. 27)) · Cedar Falls Code of Ordinances § 7-110

Corpus is an independent public-information project, not the official City of Cedar Falls website. Stable reference: corpuslaw.us/code/62b6e980-d9cf-44b1-8242-89e9fc0500ac

Sec. 7-110. - Burners firing 500,000 BTUs per hour or larger input.

Minimum requirements for burners firing 500,000 BTUs per hour or larger input are as follows: (1) All such burners must be equipped with approved electronic controls. (2) Main burner shutoff valves shall be an approved type, with handles permanently attached. (3) Main burner shutoff valves shall be rated to close against a minimum of 15 pounds per square inch gas pressure in three seconds or less. (4) Where gas pressure exceeds 15 pounds per square inch in the gas utility mains, the safety shutoff valve shall be rated to close against these pressures. (5) Electrical wiring shall provide for closing of this valve on: a. Power failure or interruption. b. Action from any safety limit switches. c. Pilot failure. (6) Two electrically operated gas valves on the main burner gas lien are required. One shall be the input control valve and the other the safety shutoff valve and each shall be so constructed that it will perform its specific job. (7) A one-eighth-inch pipe tap is to be provided with a nipple and cap in the manifold for connecting a manifold pressure gauge for test purposes. (8) A high and low gas pressure switch shall be installed downstream from the input valve and set as close to manifold pressure as possible without causing nuisance shutdowns. When used with an automatic reset type valve, this control must be equipped with a manual reset feature. When used with a manual reset type safety shutoff valve, this control may be either the automatic reset type or the manual reset type.

(Code 2017, § 7-213; Ord. No. 2321, § 2, 1-8-2001)

Ask a question about Cedar Falls law

Corpus searches the Cedar Falls sections it holds and shows the ones that match, with their citations. Free, no sign-in.