Section 5704.2.11.4.3 of the IFC is amended to read as follows: Sec. 5704.2.11.4.3 Dry sumps. Approved sampling tubes of a minimum 6" in diameter shall be installed in the backfill material of each underground flammable or combustible liquid storage tank. The tubes shall extend from a point 12" below the average grade of the excavation to ground level and shall be provided with suitable surface access caps. Each tank site shall provide a sampling sump at the corners of the excavation with a minimum of 4 sumps. Sampling tubes shall be placed in the product line excavation within 10' of the tank excavation and one every 50' routed along product lines towards the dispensers, and a minimum of two are required.