§ 14-3-1-903.2.9.3 — Amendment to Section 903.2.9.3 of the IFC
Salina Code, City of Salina, Kansas (Codified through Ordinance No. 26-11299 adopted August 24, 2026. (Supp. No. 19)) · Salina Municipal Code § 14-3-1-903.2.9.3
Corpus is an independent public-information project, not the official City of Salina website. Stable reference: corpuslaw.us/code/48ea8e66-f8eb-4df6-9f62-9edfb72c0d27
Sec. 14-3-1-903.2.9.3. - Amendment to Section 903.2.9.3 of the IFC.
Section 903.2.9.3 of the IFC is amended to read as follows: Sec. 903.2.9.3 Self-Service Storage Facilities. An automatic sprinkler system shall be installed throughout all self service storage facilities with a fire area greater than 7,500 square feet. A screen shall be installed at eighteen inches (18") below the level of the sprinkler heads to restrict storage above that level. This screen shall be a mesh of not less than one inch (1") nor greater than six inches (6") in size.
(Ord. No. 25-11266, § 1, 12-8-25)