Sec. 14-3-1-D104.2. - Amendment to Section D104.2 of the IFC.

Section D104.2 of the IFC is amended to read as follows: D104.2 Buildings exceeding 62,000 square feet in area. Buildings or facilities having a gross building area of more than 62,000 square feet (5760 m2) shall be provided with two separate and approved fire apparatus access roads. Exceptions: 1. Projects having a gross building area of up to 124,000 square feet (11,520 m2) that have a single approved fire apparatus access road where all buildings are equipped throughout with approved automatic sprinkler systems. 2. When signage requirements in D103.6 are met, and at the discretion of the fire code official, where geographical or topographical barriers such as a levee, river channel, cliff, highway, airport, military installation, industrial complex, park land, or similar prevent the installation of a second fire apparatus access road, projects having buildings or facilities of up to 93,000 square feet (8,640 m2) in building area may be approved on a single fire apparatus access road when: 1) the road is divided by a median of at least 9 feet in width, 2) the lanes on either side of the median are at least 29 feet in width back of curb to back of curb, and 3) the road provides direct access to each building and facility in the project.

(Ord. No. 25-11266, § 1, 12-8-25)

Ask a question about Salina law

Corpus searches the Salina sections it holds and shows the ones that match, with their citations. Free, no sign-in.