Sec. 14-3-1-B105.1. - Amendment to Section B105.1 of the IFC.
Section B105.1 of the IFC is amended to read as follows: Sec. B105.1 One- and two-family dwellings. The minimum fire-flow requirements for one- and two-family dwellings having a fire-flow calculation area which does not exceed 3,600 square feet (344.5 m2) shall be 1,000 gallons per minute (3785.4 L/min) for 1 hour. Fire-flow and flow duration for dwellings having a fire-flow calculation area in excess of 3,600 square feet (344.5m2) shall not be less than that specified in Table B105.1. Exceptions: a) A reduction in required fire flow of up to 50 percent, as approved, is allowed when the building is provided with an approved automatic sprinkler system. b) Exposure distance from adjacent buildings meets the requirements of National Fire Protection Association NFPA 80A, Recommended Practices for Protection of Buildings from Exterior Fire Exposures. c) Construction is on a tract of land for which final platting and zoning was in effect as of August 1, 1989. Approval of required platting and zoning shall not include approval of a final development plan in a planned development district. If rezoning of such property is conducted; whereby the rezoning use is intensified the exemption by which final platting and zoning was in effect as of August 1, 1989 shall not be used.
(Ord. No. 25-11266, § 1, 12-8-25)
Ask a question about Salina law
Corpus searches the Salina sections it holds and shows the ones that match, with their citations. Free, no sign-in.