Sec. 14-3-1-903.2.9. - Amendment to Section 903.2.9 of the IFC.
Section 903.2.9 of the IFC is amended to read as follows: Sec. 903.2.9 Group S-1. An automatic sprinkler system shall be provided throughout all buildings containing a Group S-1 occupancy where one of the following conditions exists: 1. A Group S-1 fire area exceeds 12,000 square feet (1115 m2 ). 2. A Group S-1 fire area is located more than three stories above grade plane. 3. The combined area of all Group S-1 fire areas on all floors, including any mezzanines, exceeds 24,000 square feet (2,230 m2 ). 4. A Group S-1 fire area used for the storage of commercial trucks or buses where the fire area exceeds 5,000 square feet (464 m2 ). 5. A Group S-1 occupancy used for the storage of upholstered furniture or mattresses exceeds 2,500 square feet (232 m2 ). Exception to 5: Group S-1 occupancies that are self-service storage units shall meet the requirements of Salina Municipal Code Section 14-3-1-903.2.9.3.
(Ord. No. 25-11266, § 1, 12-8-25)