§ 8-1-3-1208.10.1 — Amendment to Section 1208.10.1 of the UPC

Salina Code, City of Salina, Kansas (Codified through Ordinance No. 26-11299 adopted August 24, 2026. (Supp. No. 19)) · Salina Municipal Code § 8-1-3-1208.10.1

Corpus is an independent public-information project, not the official City of Salina website. Stable reference: corpuslaw.us/code/3bcb8f8a-d7b4-40ed-be84-fe3969f77908

Sec. 8-1-3-1208.10.1. - Amendment to Section 1208.10.1 of the UPC.

Section 1208.10.1 of the UPC is amended to read as follows: Sec. 1208.10.1 Overpressure Protection. Where piping systems serving appliances designed to operate with a gas supply pressure greater than 14 inches water column (3.5 kPA) are required to be equipped with overpressure protection by Section 1208.9, each overpressure protection device shall be adjusted to limit the gas pressure to each connected appliance as required by the appliance manufacturer's installation instructions. [NFPA 54:5.9.2.2]

(Ord. No. 25-11270, § 1, 12-8-25)