Sec. 8-1-3-814.1. - Amendment to Section 814.1 of the UPC.

Section 814.1 of the UPC is amended to read as follows: Sec. 814.1 Condensate Disposal. Condensate from air washers, air-cooling coils, condensing appliances, and the overflow from evaporative coolers and similar water-supplied equipment or similar air-conditioning equipment shall be collected and discharged to an approved plumbing fixture or disposal area. Where discharged into the drainage system, equipment shall drain using an indirect waste pipe. The waste pipe shall have a slope of not less than 1/8 inch per foot (10.4 mm/m) or 1 percent slope and shall be of an approved corrosion-resistant material not smaller than the outlet size in accordance with Section 814.3 or Section 814.4 for air-cooling coils or condensing appliances, respectively. Condensate or wastewater shall not drain over a public way. Exception: Air handling units containing a condensing unit and heating element shall be considered one unit.

(Ord. No. 25-11270, § 1, 12-8-25)