Sec. 8-1-3-1208.9. - Amendment to Section 1208.9 of the UPC.
Section 1208.9 of the UPC is amended to read as follows: Sec. 1208.9 Overpressure Protection Required. Where the serving gas supplier delivers gas at a pressure greater than 2 psi for piping systems serving appliances designed to operate at a gas pressure of 14 inches water column (3.5 kPa) or less, overpressure protection devices shall be installed. Piping systems serving equipment designed to operate an inlet pressures greater than 14 inches water column (3.5 kPA) shall be equipped with overpressure protection devices as required by the appliance manufacturer's installation instructions. [NFPA 54:5.9.1]
(Ord. No. 25-11270, § 1, 12-8-25)